BMP2 BASIC – Inverter Control Board User and Installation Manual

This page provides technical information from the official BMP2 BASIC Inverter Control Board User and Installation Manual, Revision 3.00.10 MM, software reference X.23.4302.

The documentation covers three-phase electrical connections, DIP switch settings, low-voltage terminals, operating functions, diagnostic codes, door position teaching and interlock systems.

Document Information

Manufacturer
BMP EUROPE Srl
Control board
BMP2 Inverter Control Board
Program version
BASIC
Document revision
Rev. 3.00.10 MM
Software reference
X.23.4302
Versions listed on the cover
V04, V05, V06 and V07
Versions in internal page headers
V04, V05 and V06
Languages
English and Italian
Document length
18 PDF pages
English section
Pages 1-9
Italian section
Pages 10-18

The cover includes V07, while the internal page headers identify V04/V05/V06. Before applying technical instructions, verify the hardware and software versions of the installed control board.

Electrical Specifications

Page 1 identifies the electrical characteristics of the BMP2 BASIC control system.

Specification Documented value
Power supply 208-460 V AC ±10%, 50/60 Hz, three-phase
Motor reference 2.2 kW, 50-80 Hz
Auxiliary supply 12 V DC, 1 A
Position detection Absolute encoder

Electrical characteristics and motor wiring must be checked against the actual equipment and the original installation diagrams.

Power Connections and DIP Switch SW1

Page 2 contains the three-phase power connection diagram, motor wiring arrangements, flashing lamp and brake connections.

Power and Motor Connections

  • Three-phase power supply: terminals 26, 27 and T
  • Protective ground connection: terminal 28
  • Motor connections: terminals 23, 24 and 25
  • Flashing lamp and brake: terminals 29, 30 and 31

The original diagrams distinguish motor configurations for 230 V and 380 V. The manual specifies a 103 V DC brake connection.

DIP Switch SW1 Functions

Switch Function
DIP 1 Brake control activation or deactivation
DIP 2 Negative or positive brake configuration

DIP 1 is associated with brake diagnostic codes AL0050 and AL0051. Refer to page 2 for the exact switch positions and wiring diagrams.

Low-Voltage Connections and LED Indicators

Page 3 documents control inputs, safety connections, auxiliary power and LED status indicators.

Terminal Function
1-2 12 V DC auxiliary supply
3 RGB lamp serial communication
4-5 Door status contact / interlock connection
7 Anti-jamming sensor, normally closed
8 Opening input, normally open
9 Safety light barrier, normally closed
10 UPS activation
11 START input
12 Pedestrian START input
14 Photocell, normally closed
16 STOP, normally closed
17-18 Absolute encoder connections
19 Extra run input
20 Programmable auxiliary input
21-22 Additional auxiliary power terminals
32-33 Door open status contact

Terminal assignments, contact states and the LED identifiers are specified in the original diagram on page 3.

Encoder and Inverter Software

The manual specifies the following software checks:

  • FIX_03 encoder software: version 1_7 or later
  • Inverter software: version 02.21.3805 or later

Check the installed software versions before commissioning or troubleshooting.

On-Board Control Keys

Page 4 describes the three control board keys used during positioning, teaching and menu navigation.

Key Function
P1 Jog OPEN - dead-man movement and internal menu navigation
P2 Teaching mode and parameter selection
P3 Jog CLOSE - dead-man movement and internal menu navigation

The teaching procedure is described separately on page 9.

Running Options and Operating Functions

Page 4 documents the BASIC program running options and their numerical configuration values.

Available functions include:

  • UPS activation
  • START input closing behaviour
  • Automatic closing after photocell transit
  • Pedestrian opening and closing
  • Encoder time monitoring
  • Deicing operation
  • Automatic wired interlock
  • Manual interlock
  • Wi-Fi interlock
  • Automatic START behaviour after power failure
  • Washing position
  • Radar input options
  • Alarm relay functions
  • Extra opening limit
  • Spiral door mode
  • UPS closing and manual UPS operation
  • CAPTURE radar recognition

The functions are organised into Options 1, Options 2 and Options 3. Some require an LCD programmer, UPS board or additional equipment.

Refer to page 4 for the exact values, configuration requirements and restrictions.

Alarm Codes and Fault Diagnosis

Pages 5-6 provide the BMP2 BASIC alarm reference tables. The display uses the prefix AL followed by a four-character code.

Alarm code Description
AL0004 / AL0005 Electronic control board failure
AL0011 STOP error sequence
AL0012 Motor short circuit
AL0013a-e Absolute encoder position error
AL0032 Overload
AL0050 Brake interrupted
AL0051 Brake overload
AL0052 Position below the lower limit
AL0053 Position beyond the opening limit
AL0055 Incompatible UPS version
AL0056 / AL0070 Invalid learning procedure
AL0074 Anti-jamming sensor activation
AL0076 Power supply fault
AL0079 Safety edge activation
AL007A UPS power supply fault
AL0080-AL0086 Software errors
AL0087 Overvoltage
AL008D Overtemperature
AL008F Ignition voltage fault
AL0091 / AL0093 / AL0094 / AL0095 / AL0097 Software errors
AL0103 Photocell blocked during teaching
AL010E Door stalled
AL0116 / AL0117 / AL0118 Motor configuration errors
AL0136 Encoder data communication error
AL0138 Encoder battery fault
AL013A Lost encoder position

Low-Voltage Overload Indication

Page 6 also describes repeated switching of the display and LEDs as a possible low-voltage overload or short-circuit condition.

Detailed checks and corrective actions are provided in the original alarm tables. Electrical troubleshooting must be carried out by qualified personnel.

Display Status Codes

Page 7 lists the operating status indications shown on the BMP2 display.

Display Meaning
CDoor closed
ODoor opened
OPDoor opening
CLDoor closing
PEPedestrian operation
StSTOP
JJog operation
tADoor dimension teaching
tPPedestrian opening teaching
-.-Teaching required
SEService expired
SnService approaching
UPSUPS opening
UPS-UPS mode, door remains open
UPSFUPS fault
UPSCUPS closing
UPSOUPS obstacle
ALnnnnAlarm indication
r2Partial reset at boot
r3Complete reset at boot
r4Service reset

Display Parameters with STOP Pressed

Page 7 describes the parameters available through the control board when the STOP command is active.

Parameter Function
to Automatic pause time
nO Minimum motor torque during opening
nC Minimum motor torque during closing
So Opening speed
Sc Closing speed
OP Open position adjustment
O2 Intermediate opening
CL Close position adjustment
Fo Photocell exclusion point
r1-r6 Relay contact functions
Fu Automatic closing, UPS and interlock options

The original manual specifies the adjustment ranges and the functions associated with each parameter. Some settings affect motor operation and safety devices.

Relay Contact Functions

Page 8 describes ten relay configuration cases.

Case Function
1Door open - normally open
2Door open - normally closed
3Pedestrian open - normally open
4Pedestrian open - normally closed
5Door closed - normally open
6Door closed - normally closed
7Automatic interlock
8Flashing while the door moves
9Alarm - normally closed
10 Door open indication with preflashing exclusion

Automatic, Manual and Wi-Fi Interlock

Page 8 explains the interlock system used to coordinate two or more doors.

The interlock prevents another door from opening while one connected door is open or opening.

Documented Interlock Modes

  • Automatic wired interlock
  • Manual wired interlock
  • Wi-Fi interlock with LCD programmer

In automatic interlock mode, the second door can open automatically after the first door closes.

In manual interlock mode, the second door waits for a new opening command.

Wi-Fi interlock requires the LCD programmer to remain connected. The original manual provides the wiring and configuration references.

Door Dimension Teaching and Commissioning

Page 9 describes the door dimension teaching procedure required before automatic operation.

Until teaching is completed, the control board displays -.- .

Commissioning Checks

The manual requires verification of safety input connections, photocell alignment and motor rotation before the procedure.

Opening Dimension Teaching

The procedure records the main opening position and the automatic pause time using the on-board controls.

Pedestrian Opening Teaching

The optional pedestrian procedure records a separate opening position and pause time.

Teaching-Related Alarms

Code Meaning
AL0056 / AL0070 Invalid learning procedure
AL0103 Photocell blocked during teaching
-.- Teaching not completed

Follow the complete procedure on page 9 when commissioning the equipment.

Official PDF Manual

Download the complete BMP2 BASIC Inverter Control Board User and Installation Manual, including three-phase power wiring diagrams, low-voltage terminal assignments, DIP switch functions, alarm tables, interlock documentation and door teaching procedures.

Download Official BMP2 BASIC Control Board Manual (PDF)

BMP Europe Official Documentation | English / Italian | Rev. 3.00.10 MM | 18 pages

Technical Documentation Notice

This page provides a structured reference to the official BMP2 BASIC control board manual.

It does not replace the complete manufacturer documentation.

Before applying wiring, programming or diagnostic instructions, verify the installed control board hardware, software reference and motor configuration.

Electrical installation, commissioning and fault diagnosis must be performed by qualified personnel following the official instructions and applicable safety requirements.