BMP5 – Inverter Control Board User and Installation Manual

This page provides technical information from the official BMP Europe BMP5 Inverter Control Board User and Installation Manual, Revision 1.4.0 MM, software reference 5.26.4004.

The BMP5 is an electronic inverter control board for automatic high-speed doors equipped with an absolute encoder. The manual documents the on-board UPS system, electrical connections, programming, OLED display indications, alarms and interlock functions.

Document Information

Manufacturer: BMP EUROPE Srl
Control board: BMP5
Official document: User and Installation Manual
Revision: Rev. 1.4.0 MM
Software reference: 5.26.4004
Encoder type: Absolute encoder
UPS system: On-board UPS; battery components are optional depending on configuration
Languages: English and Italian
Document length: 24 PDF pages
English section: Pages 1-12
Italian section: Pages 13-24

Technical compatibility depends on the installed board, motor, encoder, firmware and UPS configuration.

Electrical Specifications

Page 1 describes the BMP5 system and its electrical characteristics.

Specification Documented value
Power supply 208-460 V AC ±10%, 50/60 Hz, three-phase
Motor reference 2.2 kW, 50-80 Hz
Auxiliary supply 12 V DC, 1 A
Position detection Absolute encoder
Backup system On-board UPS system

The electrical ratings must be verified against the installed motor and control board identification data.

Electrical Power Connections and DIP Switch SW1

Page 2 provides the BMP5 power wiring diagram, motor connections, brake output and SW1 DIP switch functions.

Connection Description
R26 / S27 / T Three-phase power supply
28 Protective ground
23 / 24 / 25 Motor connection
30 / 31 103 V DC brake connection

SW1 DIP Switch Functions

Switch Function
DIP 1 Brake monitoring control. Related alarms: AL0050 and AL0051.
DIP 2 Negative or positive brake configuration.

The manual includes motor connection diagrams for 230 V and 380 V arrangements. The correct connections depend on the installed motor.

Page 2 also contains a warning about the required power-up procedure before connecting UPS batteries.

Refer to the original diagram and safety instructions before electrical work.

Low-Voltage Connections and LED Indicators

Page 3 documents the BMP5 low-voltage terminals, signal connections and corresponding LED indicators.

Terminal Function
1 / 2 12 V DC auxiliary supply and 0 V
3 RGB lamp serial communication
4 / 5 Door status contact or interlock connection
7 Anti-jamming sensor, NC
8 OPEN command, NO
9 Safety light barrier, NC
10 Programmable input, NO
11 START command, NO
12 Pedestrian START, NO
14 Photocell, NC
16 STOP, NC
17 / 18 Encoder A and B
19 Extra travel input
20 Programmable input, NO
21 / 22 Additional 12 V DC supply and 0 V
32 / 33 Door open status contact

Page 3 also identifies the connections for the 12 V red and green traffic lamp.

The original manual specifies the contact types and wiring requirements. Safety inputs must be configured according to the installed devices.

On-Board Control Keys

Page 4 describes the three on-board buttons.

Button Function
P1 JOG OPEN and internal menu navigation
P2 Door dimension teaching and parameter selection
P3 JOG CLOSE and internal menu navigation

P1 and P3 are used for dead-man movement during installation. Refer to the original manual for safe commissioning procedures.

Running Options

Page 4 lists the BMP5 operating options and their configuration levels.

Options 1

  • UPS function
  • START input closing behaviour
  • Automatic closing after photocell transit
  • Pedestrian opening
  • Encoder time monitoring
  • Deicing operation
  • Wi-Fi interlock
  • Automatic interlock
  • Automatic START after power interruption
  • Washing position
  • Radar input behaviour
  • Alarm relay operation

Options 2

  • Manual interlock
  • START behaviour after extra motor current
  • Extra opening limit
  • Spiral door mode

Options 3

  • UPS closing mode
  • Manual UPS opening and closing
  • CAPTURE radar recognition

The original manual provides the numerical values and configuration requirements for each function.

Door Dimension Teaching Procedures

Page 5 documents the procedure required to memorise the door opening and closing dimensions.

Before automatic movement, the motor direction and safety devices must be checked.

Main Opening

The teaching procedure records the opening position and the automatic closing pause time using the on-board controls.

The OLED display indicates TEACH during the procedure, followed by position and pause-time information.

Pedestrian Opening

A separate pedestrian opening position and pause time can also be memorised.

The extended menu allows subsequent adjustment of opening dimensions and times.

Follow the original page 5 sequence during commissioning.

BMP5 Alarm Codes and Troubleshooting

Pages 6-7 list the BMP5 alarm codes. The OLED display shows the prefix AL followed by a four-character code.

Motor, Brake and Control Board Alarms

Alarm code Description
AL0001-AL0006 Motor power-stage setup fault or electronic board failure
AL0010 / AL0012 Motor short circuit
AL0050 Brake interrupted
AL0051 Brake overload
AL0056 / AL0070 Invalid door learning
AL0074 Top sensor alarm
AL0076 Low supply voltage
AL0079 Safety edge activation
AL007B Generic error
AL0080 / AL0086 / AL0091 / AL0093 / AL0094 / AL0097 Software error
AL0087 Mains overvoltage
AL008D Overtemperature
AL008F Ignition voltage fault
AL0103 Photocell blocked during teaching
AL010E Door stalled
AL0136 Encoder data communication error
AL0138 / AL013E Encoder fault

On-Board UPS Alarm Codes

The following codes are specifically documented for the BMP5 UPS system.

Alarm code Description
AL007A UPS battery fault
AL0201 UPS battery overvoltage detected
AL0202 UPS battery disconnected
AL0203 UPS overload
AL0204-AL0206 UPS MOSFET fault
AL0207 Insufficient UPS V_BUS generation
AL0208 UPS overload detected at the end of a manoeuvre
AL0209 / AL0210 UPS circuit voltage error

Low-Voltage Protection

Page 7 also describes a possible 12 V short-circuit or overload condition indicated by repeated switching off and on of the OLED display and LEDs.

The original manual contains diagnostic checks and corrective actions for each alarm. Electrical troubleshooting must be performed by qualified personnel.

OLED Display Status Codes

Page 8 explains the information shown on the integrated OLED display.

The screen includes door status, motor current, mains voltage, UPS battery level and UPS battery status.

Display Meaning
JnJog height status
JOJog opening
JCJog closing
JOGJog mode
CDoor closed
CLDoor closing
ODoor opened
OPDoor opening
UPS- UPS activation with door already open
UPS UPS activation
STOPDoor stopped
TEACHTeaching procedure
PEDPedestrian opening
TS:nAuto-closing time
TANormal opening height teaching
TPPedestrian height teaching
nPPedestrian auto-closing time
-- Teaching missing or door status unknown

OLED Parameters with STOP Pressed

Page 8 documents the parameters accessible from the OLED menu with STOP active.

Parameter Function
to Automatic pause time, 1-99 seconds
nO Minimum opening motor torque
nC Minimum closing motor torque
So Opening speed
Sc Closing speed
OP Opening position adjustment
O2 Not used
CL Closing position adjustment
r1-r6 Relay contact functions
SL Anti-snag function and sensitivity setting
OP START closing-only option and UPS START behaviour

Page 8 specifies the adjustable parameter ranges. Some settings affect door movement and safety-related operation.

Extended Programming Menu

Pages 9-11 describe the extended programming menu and its parameters.

The menu provides configuration functions for operating options, door positions, inputs, motor characteristics, movement ramps, UPS, encoder diagnostics and control board information.

Operating Options

Documented parameters include:

  • UPS and UPS ON START
  • START closing-only mode
  • Pedestrian opening options
  • Defrost mode
  • Automatic and Wi-Fi interlock
  • Superinterlock
  • Opening at power-up
  • Cold door cleaning mode
  • Radar operating behaviour
  • Alarm relay mode
  • Spiral door configuration
  • Automatic closing
  • MEGAPACK mode

Door Position and Timing Parameters

Parameter Function
DIM OPEN Open encoder position
DIM OPEN 2 Secondary open position
DIM OPEN P Pedestrian open position
DIM CLOSE Closed encoder position
DIM SLO CL Slow closing position
DIM FREEZE Freeze position
DIM WASH Washing position
APPR OPEN Opening approach position
APPR CLOSE Closing approach position
TPAUSE Normal opening pause
TPAUSE PED Pedestrian opening pause
TQUEUE PHC Photocell queue time
T NOFROST Antifreeze pause time

Input and Relay Configuration

Page 10 identifies input assignments for START, pedestrian START, radar, photocells, safety edge, anti-jamming, interlock and manual/automatic operation.

The extended menu also provides relay assignment functions and signal filtering for inputs 9 and 14.

Motor, Ramps and UPS Parameters

The documented parameter groups include:

  • Motor minimum opening and closing voltage
  • Motor phase current monitoring
  • Opening and closing frequencies
  • Slow movement frequencies
  • Acceleration and deceleration times
  • UPS generation time
  • Minimum UPS voltage
  • UPS starting and running frequencies
  • UPS battery voltage

Encoder and Board Diagnostics

Page 11 documents hardware, firmware, battery and diagnostic information for the encoder and control board.

The available information includes:

  • Hardware and firmware versions
  • Encoder and board serial numbers
  • Encoder battery voltage
  • Magnetic field measurements
  • Temperature measurements
  • Encoder status and active alarms
  • Alarm history
  • Door operating cycles
  • DC bus voltage
  • Brake current

The complete parameter names and navigation diagrams are provided on pages 9-11.

Relay Contact Functions

Page 12 provides ten relay configuration cases.

Case Function
1Door open - NO
2Door open - NC
3Pedestrian open - NO
4Pedestrian open - NC
5Door closed - NO
6Door closed - NC
7Automatic interlock
8Flashing while moving
9Alarm - NC
10 Door open indication with preflashing exclusion

Automatic, Manual and Wi-Fi Interlock

Page 12 describes the interlock function used to coordinate two or more doors.

The system prevents another connected door from opening while one door is open or opening.

Automatic Interlock

The automatic wired interlock can open the second door after the first door has returned to the closed position.

Manual Interlock

In manual interlock mode, the second door waits for a new opening command.

Wi-Fi Interlock

The manual also documents wireless interlock through the LCD programmer.

The Wi-Fi interlock requires the programmer to remain connected to the control boards.

The original page 12 contains the wiring diagram and programming references.

Official PDF Manual

Download the complete BMP5 Inverter Control Board User and Installation Manual, including power wiring diagrams, on-board UPS information, alarm codes, OLED display indications, extended menu parameters, relay functions and interlock instructions.

Download Official BMP5 Control Board Manual (PDF)

BMP Europe Official Documentation | English / Italian | Rev. 1.4.0 MM | Sw. Ref. 5.26.4004 | 24 pages

Technical Documentation Notice

This page provides a structured reference to the official BMP5 User and Installation Manual.

It does not replace the complete manufacturer documentation.

The original PDF is the reference for electrical diagrams, UPS connections, configuration settings and safety procedures.

Before applying technical instructions, verify the actual board version, software reference, motor and UPS configuration.

Installation, programming, maintenance and electrical troubleshooting must be performed by qualified personnel.