DynamicRoll CB230 – Technical Data Sheet
BMP Europe / Technical Data Sheets
BMP DynamicRoll CB230 is a self-repairing industrial high-speed roll-up door designed to separate sterile and pressure-controlled environments, including areas maintained at positive air pressure.
Its sealing system helps limit uncontrolled air leakage between adjacent spaces, supporting ventilation and air purification systems. The door incorporates a counterweight system that allows emergency opening in the event of a power failure.
This page presents selected specifications from the DynamicRoll CB230 Lite technical data sheet, including performance, air permeability, control and safety equipment, curtain materials and accessories.
Product Overview
High-speed cleanroom door with counterweight emergency opening.
DynamicRoll CB230 uses a patented sliding system with high-density, self-lubricating Polyzene guides and a zipper integrated into the flexible PVC curtain. After an impact, the curtain can leave the side guides and reinsert during the following operating cycle. The curtain has no rigid horizontal reinforcement elements.
Technical Specifications
Published performance and construction data from the official Lite data sheet.
| Maximum dimensions | W 4,500 mm × H 4,500 mm |
|---|---|
| Maximum opening speed | Up to 2.5 m/s |
| Closing speed | 0.8 m/s |
| Cycle test | 1,000,000 cycles |
| Air permeability | Class 2; Class 5 with the optional patented magnetic sealing system |
| Structure | Not self-supporting |
| Frame and motor cover hood | Standard: galvanized steel. Optional: powder-coated steel or stainless steel 441/316 |
| Standard curtain | PVC curtain, 900 g/m² |
| Optional curtain types | Insulated, translucent (35–40%), FDA white, antistatic |
| Sliding system | Patented zipper-guided system with high-density, self-lubricating Polyzene |
| Wiring | Plug-and-play system, IP65 |
| Emergency opening | Standard: counterweight system. Optional: UPS battery |
Air Permeability and Cleanroom Applications
Controlled air leakage in pressurised environments.
The CB230 is designed for cleanroom and other pressure-controlled installations where separating areas while limiting air leakage is important. The optional magnetic sealing system provides a Class 5 air permeability configuration. The manufacturer also references testing at a pressure differential of 50 Pa.
- Designed for sterile and overpressurised environments
- Optional magnetic sealing system for low air permeability
- Counterweight arrangement for emergency opening
- Self-repairing flexible curtain without rigid horizontal elements
Air permeability classes describe the door's leakage performance and should not be confused with ISO 5 cleanroom classification. Verify the selected configuration and test documentation for the intended application.
Control System and Safety
Power supply, control electronics and safety devices.
| Standard control box | Powder-coated steel, IP54, 300 × 500 × 150 mm |
|---|---|
| Optional control boxes | Stainless steel; PVC box IP65, 300 × 400 × 150 mm |
| Control electronics | Inverter system 50/60 Hz with absolute encoder |
| Power supply options | Single-phase 230 V, max 16 A; three-phase 400 V, max 10 A; three-phase 230 V, max 16 A |
| Control functions | Start/Stop button; two free contacts for door open, door closed and alert; automatic/manual interlocking between two doors |
| Motor and control panel protection | IP54 |
| Standard safety devices | Photocell set IP65, anti-jam reverse sensor, wireless safety edge IP65 |
| Optional safety device | Multi-ray light curtain H2500, IP67 |
Standard PVC Curtain Characteristics
Material composition and tests from the manufacturer's data sheet.
| External material | Opaque PVC, 0.7 mm; 18 standard colours |
|---|---|
| Internal material | Rough PVC, 0.2 mm; 18 standard colours |
| Fabric | PES, one fabric layer, 1100 Dtex, 12 × 12 |
| Tested thickness | 0.9 ± 0.1 mm, ISO 2286-3 |
| Reported material weight | 900 g/m²; 0.90 ± 0.1 kg/m², ISO 2286-2 |
FDA-Designated Curtain Material
PUR-coated white fabric described in the Lite data sheet.
| Coating | White polyurethane (PUR) on both sides |
|---|---|
| Coating thickness | 0.6 mm on each side |
| Fabric | PET, one fabric layer, 2200 Dtex, 12 × 12 |
| Tested thickness | 1.20 ± 0.1 mm, ISO 2286-3 |
| Tensile strength, warp | 6,000 N / 50 mm, ISO 1421 |
The FDA-designated material table reports 1,500 g/m² in one weight entry and 1.30 ± 0.1 kg/m² in another. Confirm the applicable weight and regulatory documentation before selecting this material.
Transparent Window Characteristics
Superclear PVC window specifications.
| Material | PVC Superclear 0.75 mm FR |
|---|---|
| Thickness | 0.75 mm |
| Total PVC weight | 940 g/m² |
| Light transmission | 87.5%, JIS K 7361 |
| Temperature limitation | Suitable only for positive-temperature environments |
The positive-temperature limitation refers specifically to the Superclear window material described above. The original PDF contains a separate, ambiguous statement about the door's operating temperature that should be clarified with BMP Europe.
Optional Accessories
Sensors, opening devices and traffic control equipment.
- TOF/Spot opening point radar for internal use
- Infrared radars for cross-movement, motion and presence detection
- Fixed red and green traffic lights, LED countdown signals and barriers
- Opening buttons, freeze-stop and no-touch controls
- Dual-function traffic-light button for opening and closing indications
- Wind gauge, key selector, remote control and B-Protect bollard
- Pull-cord switch and magnetic loop detector
Technical Documentation
Access the public DynamicRoll CB230 Lite technical data sheet or request the complete product documentation.
Public DocumentationThe Lite PDF includes published performance, sealing characteristics, control and safety equipment, curtain materials and optional accessories.
Download Lite Technical Data Sheet (PDF)Need More Detailed Technical Information?
The complete BMP DynamicRoll CB230 technical data sheet is available through the official product download request form. Complete the form to access the full documentation.
Request Complete Technical Data Sheet