BMP TLR V04 – High-Speed Door Control Unit Manual

This page provides technical information from the official BMP TLR V04 control unit manual, document version V1.13.

The BMP TLR V04 is an electronic control board designed to operate industrial high-speed folding doors equipped with mechanical limit switches or an absolute encoder.

The documentation covers electrical connections, DIP switch functions, programming procedures, operating modes, display indications and fault diagnosis.

Document Information

Manufacturer: BMP EUROPE Srl
Control unit: BMP TLR V04
Document version: V1.13
Document type: Control Unit Installation Instructions and Warnings for Installers
Original language: Italian
Document length: 6 PDF pages
Position detection systems: Mechanical limit switches or absolute encoder

Control Unit Application

The BMP TLR V04 is designed to control high-speed folding door automation using mechanical limit switches or an absolute encoder for position detection.

The control unit manages motor operation, opening and closing commands, pedestrian opening, safety inputs and door status signalling.

Compatibility with individual BMP door models must be verified against the installed equipment and its electrical configuration.

Electrical Connections and Terminal Layout

Pages 1 and 4 of the manual contain electrical wiring diagrams and terminal descriptions for the BMP TLR V04 control board.

The documented connections include:

  • 230/400 VAC power supply terminals
  • Opening and closing contactor outputs
  • Motor brake connections
  • Flashing lamp output
  • Photocell and STOP inputs
  • Safety edge input
  • START and pedestrian opening commands
  • Absolute encoder channels A and B
  • Opening and closing limit switch inputs
  • Door status signalling contacts

The original diagrams identify the terminal numbers, contact types and corresponding wiring arrangements.

Electrical installation and modification must be performed by qualified personnel following the manufacturer's wiring diagrams and the configuration of the installed unit.

DIP Switch Configuration

Page 2 describes the ten DIP A switches used to configure the operating functions of the BMP TLR V04 control board.

DIP Function
1 START and pedestrian command behaviour, including automatic reclosure.
2 Photocell monitoring when starting from the closed position.
3 Opening command and man-present operation.
4 Interlock (BUSSOLA) operation and contact 12-13 function.
5 Absolute encoder or mechanical limit switch configuration.
6 Door status signalling through contacts 30-31.
7 Manual or automatic interlock operation.
8 Safety edge input configuration.
9 Photocell input configuration.
10 Closing command and man-present operation.

Refer to page 2 of the official manual for the exact ON/OFF settings and their effects.

DIP switches 8 and 9 control safety-related inputs. Their configuration must be checked against the installed safety devices and the manufacturer's instructions.

Initial Programming and Learning Procedure

Page 3 describes the mandatory initial programming procedure for the BMP TLR V04.

The procedure includes checking input indicators, positioning the door, learning its opening and closing travel and configuring the operating cycle.

Programming Procedures

  • Total working time and travel learning (mandatory).
  • Pedestrian opening programming (optional).

The learning procedure depends on whether the automation uses mechanical limit switches or an absolute encoder.

Follow the original programming flowcharts on page 3 when commissioning the control unit.

On-Board Programming Menu

Page 6 describes the menu used to adjust travel positions, pause times and display the number of completed operating cycles.

Parameter Function
LO Limit Open - opening position adjustment
LC Limit Close - closing position adjustment
LP Limit Pedestrian - pedestrian opening position adjustment
nP Normal Pause - normal opening dwell time
PP Pedestrian Pause - pedestrian opening dwell time
On Openings Number - total operating cycle count

Menu navigation uses the P_Test, P_Apre and P_Chiude buttons while the control board is in the STOP state.

Refer to page 6 for the complete parameter selection, modification and confirmation procedures.

Display Status Codes

Page 5 lists the operating status codes displayed by the BMP TLR V04 control unit.

Code Meaning
CH Door closed
CL Door closing
OP Door opening
AP Door open
tE Self-learning with absolute encoder
FC Self-learning with limit switches
ST STOP pressed

Error Codes and Fault Diagnosis

Page 5 identifies the blocking errors and non-blocking alarms documented for the BMP TLR V04.

Blocking Errors

Code Description
E1 Communication error with the absolute encoder.
E2 Motor stall. In absolute encoder configuration, motor operation is detected without corresponding door movement.
E3 Absolute encoder backup battery voltage below the permitted level.
E4 Memory write error.
E5 Microcontroller (CPU) fault.

Non-Blocking Alarm

Code Description
A3 The absolute encoder reports its factory default position, or the backup battery or its connection has been removed.

Blocking errors and non-blocking alarms require different recovery procedures. Follow the official instructions on page 5 before performing troubleshooting, resetting the board or repeating learning.

Interlock (BUSSOLA) Function

The BMP TLR V04 supports interlock operation between two control units.

Page 2 contains the connection diagram and relevant DIP switch settings for manual and automatic interlock operation.

Refer to the original documentation for the terminal connections and configuration requirements.

Official PDF Manual

Download the official BMP TLR V04 control unit manual, including electrical wiring diagrams, terminal identification, DIP switch functions, programming flowcharts, display codes and troubleshooting information.

Download TLR V04 Manual (PDF - Italian)

BMP Europe Official Documentation | Italian | Version V1.13 | 6 pages

Technical Documentation Notice

This page provides an English-language reference to the official Italian BMP TLR V04 technical manual.

The original PDF remains the reference for electrical diagrams, configuration settings, programming and safety procedures.

Installation, programming and maintenance must be carried out by qualified personnel in accordance with the manufacturer's instructions and the installed equipment.